HIP3300
100-500kVA
HIP3300 series UPS is developed as a high frequency large capacity tower UPS which adopting similar modular design thought, excellent performance parameters, higher efficiency, more reliable, maily used in medium and large data center, bank/security settlement center, dispatching center, control center, management center fields and so on. Parallel.
General Features
● DSP-controlled technology
● Parallel redundancy up to 4 units
● Wide input voltage and frequency range
● Easy-to-operate LCD display
● High power density up to 500kVA for space saving
● High input power factor and low input distortion
● Output power factor at 0.8(0.9 optional)
● ECO mode for energy saving
● Common or separate battery
● Programmable battery voltage from ±192Vdc to±240Vdc
● Intelligent charge modes with smart charge current adjustment
● Megatec/ModBus protocol supported
● Powerful charger built in
● Versatile communication interfaces provided for different applicati
● Superior overload capability
● Programmable control and monitoring software
Technical Specification
MODEL | HIP3310H | HIP3312H | HIP3316H | HIP3320H | HIP3325H | HIP3330 | HIP3340 | HIP3350 | |
Capacity (VA/Watts) | 100k / 80k | 120k / 96k | 160k / 128k | 200k / 160k | 250k / 200k | 300k / 240k | 400k / 320k | 500k / 400k | |
INPUT | |||||||||
Nominal voltage | 380/400/415Vac(3Ph+N+PE) | ||||||||
Operating voltage range | 208~478Vac for half load; 305~478Vac for full load | ||||||||
Operating frequency range | 40~70Hz | ||||||||
Power factor | ≥0.99 | ||||||||
Harmonic distortion (THDi) | 3%(100% non-linear load) | ||||||||
Bypass voltage range | 380Vac Max.voltage: +25%(optional +10%,+15%,+20% ) 400Vac Max.voltage: +20% (optional +10%,+15%) 415Vac Max.voltage: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
||||||||
Bypass frequency range | Frequency synchronize tracing range:±10% | ||||||||
Generator access | Support | ||||||||
OUTPUT | |||||||||
Rated voltage | 380/400/415Vac(3Ph+N+PE) | ||||||||
Power factor | 0.8/0.9(Customized) | ||||||||
Voltage regulation | ±1% | ||||||||
Frequency | Line mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | |||||||
Bat. mode | (50/60±0.2%)Hz | ||||||||
Crest factor | 3:1 | ||||||||
Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non-linear load |
||||||||
Efficiency | 95.00% | ||||||||
BATTERY | |||||||||
Battery voltage | Standard unit: ±216Vdc; Long run unit optional voltage: ±192 / ±204 / ±216 / ±228 / ±240Vdc | ||||||||
Charging current(A) (Charging current can be set according to battery capacity installed) |
30A (Max.) | 40A (Max.) | 50A (Max.) | 70A (Max.) | 80A (Max.) | 100A (Max.) | 130A (Max.) | ||
SYSTEM FEATURES | |||||||||
Transfer time | Utility to battery:0ms; Utility to bypass:0ms | ||||||||
Overload | Line mode | Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% turn to bypass mode immediately | |||||||
Bat. mode | Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% shut down UPS immediately | ||||||||
Short circuit | Hold whole system | ||||||||
Overheat | Line mode: Switch to bypass; Backup mode: Shut down UPS immediately | ||||||||
Low battery voltage | Alarm and switch off | ||||||||
Self-diagnostic | Upon power on and software control | ||||||||
EPO (optional) | Shut down UPS immediately | ||||||||
Battery | Advanced battery management | ||||||||
Noise suppression | Complies with EN62040-2 | ||||||||
Audible & Visual | Line failure, Battery low, Overload, System fault | ||||||||
Status LED & LCD display | Line mode, Bypass mode, Battery low, Battery bad, Overload & UPS fault | ||||||||
Reading on the LCD display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage & Inner temperature | ||||||||
Communication interface | USB,RS232,RS485,Parallel,Intelligent slot,Relay card(optional),SNMP card(optional) | ||||||||
ENVIRONMENT | |||||||||
Operating temperature | 0~40℃ | ||||||||
Storage temperature | -25~55℃(No battery) | ||||||||
Humidity range | 0~95% (Non-condensing) | ||||||||
Altitude | <1500m. When >1500m, derating power for use | ||||||||
Noise level | <65dB | <70dB | <73dB | ||||||
PHYSICAL | |||||||||
Dimension D×W×H (mm) | 850×600×1600 | 850×600×2000 | 850×1200×2000 | ||||||
Net weight (kg) | 320 | 322 | 360 | 415 | 555 | 590 | 880 | 980 | |
STANDARDS | |||||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | ||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |