YDC3300
10-80kVA
 
YDC3300 series UPS is a three phase in and three phase out high frequency UPS with medium and large power capacity, higher power density, smaller footprint, which takes the leading position in the UPS industry with same power capacity; Adopting unique power unit redundancy design technology, decrease the abnormity risk of system after single-point failure, greatly increase the system reliability. For user, it is your best choice with high investment rate.
General Features

● Online double conversion

● Output transfer time is 0ms

● PFC technology

● Full digital control(DSP)

● Output power factor: 0.9

● Input current harmonic: 3%

● Support economic (ECO) operation mode

● Optimization battery group, the quantity of battery: 10-30k(16/18/20 pcs optional), 40-80k(32/34/36/38/40 pcs optional)

● Wide input voltage range: 208~478Vac

● Wide input frequency range: 40~70Hz

● Cold start

● Communication port: USB, RS232, RS485, Parallel port, Dry contact

● Options: SNMP card/Relay card

● LCD/LED double display

● Intelligent charging management

● EPO function

● Common battery group

● The output can meet 100% unbalanced load

Technical Specification
MODEL YDC3310S/H YDC3315S/H YDC3320S/H YDC3330S/H YDC3340 YDC3360 YDC3380
Capacity (VA/Watts) 10k / 9k 15k / 13.5k 20k / 18k 30k / 27k 40k / 36k 60k / 54k 80k / 72k
INPUT
Nominal voltage 380/400/415Vac(3Ph+N+PE)
Operating
voltage range
208~478Vac
Operating
frequency range
45~55Hz at 50Hz / 54~66Hz at 60Hz(auto sensing) 40~70Hz
Power factor ≥0.99
Bypass voltage
 range
380Vac Max.voltage: +25%(optional +10%,+15%,+20% )
400Vac Max.voltage: +20% (optional +10%,+15%)
415Vac Max.voltage: +15% (optional +10%)
Min.voltage: -45% (optional -20%,-30%)
Bypass frequency
range 
Frequency synchronize tracing range:±10%
ECO range Same as the bypass
Harmonic
distortion (THDi)
≤3%(100% non-linear load)
OUTPUT
Rated voltage 380/400/415Vac(3Ph+N+PE)
Power factor 0.9
Voltage
 regulation
±1%
Frequency Line mode ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)
Bat. mode 50/60(±0.1)Hz
Crest factor 3:1
Harmonic
distortion
 (THDv)
≤2% with linear load
≤5% with non-linear load  
Efficiency 93.50% 94.50%
BATTERY
Battery voltage Standard unit:
 ±120Vdc
(20pcs 12V9Ah);
Long run unit optional voltage: ±96/±108/
±120Vdc(16/18/20
pcs optional)
Standard unit:
 ±120Vdc(2×20pcs 12V9Ah);
Long run unit optional voltage: ±96/±108/±120Vdc(16/18/20
 pcs optional)
Standard unit:
±120Vdc(3×20pcs 12V9Ah);Long run unit
 optional voltage: ±96/±108/±120Vdc(16/18/20pcs optional)
Optional voltage:
±192/±204/±216/±228/±240Vdc
(32/34/36/38/40 pcs optional)
Charging current
(A)(Charging
 current can be
 set according to
 battery capacity
   installed)
Standard unit: 1.35A
Long run unit:
Max.current 10A
Standard unit: 2.7A
Long run unit:
 Max.current 10A
Standard unit: 4.05A
Long run unit:
Max.current 15A
Max.current
15A
Max.current
30A
Max.current
 30A
SYSTEM FEATURES
Transfer time Utility to battery:0ms; Utility to bypass:0ms
Overload Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode
Short circuit Hold whole system
Communication
 interface
USB, RS232, RS485, Parallel port, REPO port, Dry contact, Intelligent slot, SNMP card(optional),
Relay card (optional), LBS port(only 60-80k)
ENVIRONMENT
Operating
 temperature
0~40℃
Storage
temperature
-25~55℃(No battery)
Humidity range 0~95% (Non-condensing)
Altitude <1500m. When >1500m, derating power for use
Noise level <55dB <58dB <63dB
PHYSICAL
Dimension
D×W×H (mm)
828×250×868 828×360×868
Net weight (kg) 115/57 170/63 171/64 223/71 73 118 122
STANDARDS
Safety  IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8