HP900C-RM
1-3kVA
HP900C-RM 1-3kVA is small power UPS of KSTAR, both input and output are single phase, the output power factor is 0.8.
General Features
● High frequency and double conversion online technology
● Fully digitized microprocessor control
● Wide input voltage range
● LCD display
● UPS start up without battery
● Cold start
● Advanced battery management
● Automatic battery charging in UPS off mode
● Lightning and surge protection
● Short circuit and overload protection
● Fan speed adjusted by load automatically
● Network/fax/modem surge protection
● Optional extension battery pack
● Battery voltage display
● Load capacity display
● EMI/RFI noise filter
● Smart RS232 communication with monitoring software
● Optional SNMP card slot
● EPO function (optional)
● Input L and N reversed alarm function
Technical Specification
MODEL | HP910C-RM | HP920C-RM | HP930C-RM | ||
Capacity (VA/Watts) | 1000/800W | 2000/1600W | 3000/2400W | ||
INPUT | |||||
Nominal Voltage | 200/208/220/230/240Vac | ||||
Operating voltage range |
110~300Vac | ||||
Operating frequency range |
46~54Hz or 56~64Hz(Auto sensing) | ||||
Power Factor | ≥ 0.99 | ||||
OUTPUT | |||||
Output Voltage | 200/208/220/230/240Vac | ||||
Output frequency | Sychronized with the utility on AC mode; 50Hz/60Hz±0.2% on battery mode | ||||
Harmonic distortion (THDv) |
<3% (Linear load) | ||||
Crest Factor | 3:1(Linear load) | ||||
Waveform | Pure Sinewave | ||||
Transfer Time | AC to DC | Zero | |||
Inverter to bypass |
4ms(Typical) | ||||
EFFICIENCY | ≥88% | ≥90% | |||
BATTERY | |||||
DC voltage | 36Vdc | 96Vdc | |||
Battery type & number | 12V/7Ah×3 | 12V/7Ah×8 | |||
Backup time(50% load) | 12min | 19min | 16min | ||
Backup time(full load) | 5min | 8min | 5min | ||
Charging current (standard unit) |
1A | 0.7A | 0.7A | ||
Charging current (long run unit) |
7A | 6A | 6A | ||
Typical recharging time | 8 hours(to 90% of full capacity) | ||||
SYSTEM FEATURES | |||||
LCD indication | 1. Input voltage/Frequency, Battery voltage, Output voltage/Frequency, Load watt/VA and percent, Inverter temperature 2. Operation mode such as“online”,“on batt”, or “or bypass” |
||||
LED indication | 1、Green LED means normal running of the UPS. 2、Yellow LED means warning of the UPS. 3、Red LED means fault of the UPS. |
||||
Overload capability | 1. >110%, 30s turn to bypass mode; 2. >150%, 300ms turn to bypass mode |
||||
Transfer time | Between AC mode and battery mode : 0ms Between AC mode and bypass mode : 4ms (Typical value 2.5ms) |
||||
Communication interface | RS232 ; SNMP (optional) | ||||
ENVIRONMENT | |||||
Operating temperature | 0~40℃ | ||||
Storage temperature | -25~55 ℃ | ||||
Humidity ranges | 0~95% (Non-condensing) | ||||
Altitude | <1500m | ||||
Noise level | <45dB | ||||
PHYSICAL | |||||
Dimension D×W×H (mm) (Standard unit) |
440×440×88 | 440×440×176 | 440×440×176 | ||
Dimension D×W×H (mm) (Long run unit) |
440×440×88 | 440×440×88 | 440×440×88 | ||
Packing D×W×H (mm) | 580×580×248 | 580×580×248 for UPS and battery cabinet Individual | |||
Net/Shipping weight (kg) (Standard unit) |
15.5/16 | 34/36 | 35/37 | ||
Net/Shipping weight (kg) (Long run unit) |
8/10 | 19/21 | 20/22 | ||
STANDARDS | |||||
Safety | IEC/EN62040-1;IEC/EN60950-1 | ||||
EMC | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5; IEC61000-4-6;IEC61000-4-8 |