MEMOPOWER Plus RT II
6-10kVA
MEMOPOWER PLUS II 6-10kVA is new generation single phase UPS. Output factor is up to 0.9. It can supply reliable power to data center, crucial load, meet the high reliability of customer for UPS, It is with high efficiency and can supply comprehensive power protection for user.
General Features
● Online double conversion
● No output transfer time
● PFC technology
● Full digital control (DSP)
● Output power factor: 0.9
● ECO function
● Charging/Rectifier/Inverter fully digital control technology
● Optimization battery group, the quantity of battery : 16/18/20 pieces (optional)
● Wide input voltage range: 120~276Vac
● Wide input frequency range: 45~55Hz/54~66Hz±0.5Hz
● Self-testing when UPS startup
● Input over/under-voltage protection
● Automatic bypass
● DC start
● Communication port: RS232 , USB
● Options: SNMP card / Relay card
Technical Specification
MODEL | MP RT 6KVA | MP RT 10KVA | ||||
Capacity (VA/Watts) | 6K/5.4K | 10K/9K | ||||
INPUT | ||||||
Nominal Voltage | 220/230/240Vac(L+N+PE) | |||||
Operating Voltage Range | 120~276Vac | |||||
Frequency Range | 45~55Hz/54~66Hz±0.5Hz | |||||
Power Factor | ≥0.99 | |||||
Bypass voltage range | 220V: +25%(optional +10%,+15%,+20% ) Bypass voltage range 230: +20% (optional +10%,+15%) 240: +15% (optional +10%) Min. voltage: -45% (optional -20%,-30%) |
|||||
Bypass frequency range | Frequency protection range:±10% | |||||
ECO range | Same as the bypass | |||||
Harmonic distortion (THDi) | <3%(100% linear load) | |||||
Generator input | Support | |||||
OUTPUT | ||||||
Output Voltage | 220/230/240Vac | |||||
Power Factor | 0.9 | |||||
Voltage Regulation | ±2% | |||||
Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | ||||
Bat. Mode | 50/60(±0.1)Hz | |||||
Crest Factor | 3:1 | |||||
Harmonic Distortion (THDv) | ≤2% with linear load | |||||
≤5% with non-linear load | ||||||
Efficiency | >93.5% | |||||
BATTERY | ||||||
Battery voltage | Optional Voltage: ±96/±108/±120Vdc | |||||
Typical recharging time | 6~8 hours (to 90% of full capacity) | |||||
Backup time | Long run unit depends on the capacity of external batteries Estimated remaining time displayed on the LCD |
|||||
Charging current | Maximum current 10A; Charging current can be set according to battery capacity installed. |
|||||
SYSTEM FEATURES | ||||||
Transfer time | Utility to battery : 0ms; Utility to bypass: 0ms | |||||
Overload | Line Mode | Load≤110%: last 60min; ≤125%: last 10min; ≤150%: last 1S;>150% turn to bypass mode | ||||
Bypass Mode | 40A(Breaker) | 60A(Breaker) | ||||
Short circuit | Hold whole system | |||||
Overheat | Line Mode: Turn to Bypass; Bat. Mode: Shut down UPS immediately | |||||
Battery low | Alarm and switch off | |||||
Self-diagnostics | Upon power on and software control | |||||
EPO (optional) | Shut down UPS immediately | |||||
Battery | Advanced battery management | |||||
Noise suppression | Complies with EN62040-2 | |||||
Audible & Visual alarms | Line failure, Battery low, Overload, System fault | |||||
Status LED & LCD display | Line mode, Backup mode, Eco mode, Bypass mode, Battery under voltage, Battery bad, Overload & UPS fault | |||||
Reading on the LCD display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time |
|||||
Communication interface | USB,RS232,Parallel port, SNMP card/Relay card (optional) |
|||||
ENVIRONMENT | ||||||
Operating temperature | 0℃~40℃ | |||||
Storage temperature | -25℃~55℃ | |||||
Humidity range | 0~95% (non-condensing) | |||||
Altitude | < 1500m | |||||
Noise level | <55dB | |||||
PHYSICAL | ||||||
Dimension W×H×D (mm) | 443×131×580(3U) | |||||
Net weight (kg) | 23 | 25 | ||||
STANDARDS | ||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |