Home >  OEM/ODM > 데이터 센터 산업 > ups> 모듈 타입 데이터 센터> HPM (6-200kVA)
HPM
6-200kVA
   
HPM series UPS is developed as a high frequency on line modular UPS for medium and large data center, adopting fully digital control technology, fully guarantee power supply to operate reliably and stably; diversified option of modular power, accurately position user side requirements; flexible redundancy design greatly increase the system availabity, user can realize expansion as demand, and modular structure greatly increase the convenience for maintenance.

General Features

● Adopting digital control design, and the control system is more reliable

● High power density design, capacity of single power module is 6KVA/ 10KVA/ 15KVA/ 20KVA/ 25KVA/ 30KVA/ 40KVA, the height of all these modules is 3U.The power of system ranged from 6KVA to 520KVA corresponds to the number of parallel power modules from 1 to 13

 Redundant control system, each power module is equipped independent control system, and control itself independently according to the sharing message, and the fault module separates from the system automatically

 Support parallel expansion for cabinet, and  parallel expansion is up to 4 cabinets.

 Voltage of batteries can be configured flexibly, 1 input 1 output/ 3 input 1 output ±96Vdc/ ±108Vdc/ ±120Vdc(16/18/20PCS)selectable; 3 input 3 output±216Vdc/±228Vdc/±240Vdc (32/34/ 36/38/40PCS) selectable

 Intelligent charging mode, Charging current can be configured , there are 3 charging mode  which are constant current mode、constant voltage mode、floating charging mode, and the charging mode can be transfer smoothly.

Technical Specification
MODEL HPM1106-30KVA HPM1110-50KVA HPM3106-30KVA HPM3110-50KVA HPM3110-100KVA HPM3320-60KVA HPM3320-100KVA HPM3320-200KVA
Capacity (VA/Watts) UPS cabinet  6~30k / 4.8~24k 6~50k / 4.8~40k 6~30k / 4.8~24k 6~50k / 4.8~40k 6~100k / 4.8~80k 10~60k / 9~54k 10~100k / 9~90k 10~200k / 9~180k
HPM module     6k / 4.8k,  10k / 8k  10k / 9k, 15k / 13.5k, 20k / 18k
INPUT
Nominal voltage 220/230Vac 380/400Vac (3Ph+N+PE) or 220/230Vac 380/400/415Vac, (3Ph+N+PE) 
Operating voltage range 120~276Vac 208~478Vac or 120~276Vac 208~478Vac for half load; 305~478Va c for full load 
Operating frequency range 40~70Hz
Power factor ≥0.99
Harmonic distortion (THDi) 5%(100% non-linear load) 2%(100% non-linear load)
Bypass voltage range 220Vac Max.voltage: +25%(optional +10%,+15%,+20% )
230Vac Max.voltage: +20% (optional +10%,+15%)
240Vac Max.voltage: +15% (optional +10%)
Min.voltage: -45% (optional -20%,-30%)
380Vac Max.voltage: +25%(optional +10%,+15%,+20% )
400Vac Max.voltage: +20% (optional +10%,+15%)
415Vac Max.voltage: +15% (optional +10%)
Min.voltage: -45% (optional -20%,-30%)
Bypass frequency range  Frequency synchronize tracing range:±10%
Generator access Support
OUTPUT
Rated voltage 220/230Vac 380/400/415Vac(3Ph+N+PE)
Power factor 0.8 0.9/1(Customized)
Voltage regulation ±1%
Frequency Line mode ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)
Bat. mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load
≤5% with non-linear load  
Efficiency 93.50% 95.50%
BATTERY
Battery voltage  ±96/±108/±120Vdc; Battery quantity(optional) ±192/±204/±216/±228/±240Vdc; Battery quantity(optional)
Charging current(A) UPS cabinet  30A (Max.) 60A (Max.) 30A (Max.) 60A (Max.) 18A (Max.) 30A (Max.) 60A (Max.)
HPM module  6A (Max.) (Charge current can be set according to battery capacity installed)
Backup time Depends on the capacity of external batteries
SYSTEM FEATURES
Transfer time Utility to battery:0ms; Utility to bypass:0ms
Overload Line mode Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% turn to bypass mode immediately
Bat. mode       Load≤110%: last 30S,≤125%: last 1S,≤150%: last 200ms,≥150% shut down UPS immediately Load≤110%: last 10min,≤125%: last 1min,≤150%: last 1S,≥150% shut down UPS immediately
Bypass mode  Breaker (6kVA:40A / 10kVA:60A)  Breaker (10kVA:20A / 15kVA:32A / 20kVA:40A)
Short circuit Hold whole system
Noise suppression Complies with EN62040-2
Communication interface UPS cabinet : RS232, RS485, Dry contact, Intelligent slot x 2(SNMP card,Relay card optional);
HPM series UPS module: RS232 
ENVIRONMENT
Operating temperature 0~40℃
Storage temperature -25~55℃
Humidity range 0~95% (Non-condensing)
Altitude <1500m. When >1500m, derating power for use
Noise level <55dB <65dB
PHYSICAL
Dimension D×W×H (mm) UPS cabinet  840×600×1400  840×600×2000  840×600×1400 840×600×2000  840×600×1400 1100×600×2000 
HPM module  443x580x131 (3U)
Net weight (kg) UPS cabinet  138 150 138 150 213 149 152 290
HPM module  6kVA/23; 10kVA/25 10kVA/26; 15kVA/30; 20kVA/31
STANDARDS
Safety  IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8